Blauberg KOMFORT EC S5B 270-E S21

Heat and energy recovery air handling units
  • Sound pressure level LpA at 3 m: 34 dB(A)
  • Heat exchanger type: Counter flow
  • Extract filter: G4
  • Supply filter: G4 (option: F8)
  • Sound-insulated casing
  • Motor type: EC
  • Enthalpy heat exchanger
  • Bypass: Auto
  • Preheater: Optional
  • Reheater: Optional
  • BMS protocol: ModBus
  • Control: Smartphone
  • Casing material: EPP
  • Humidity sensor: Optional
  • CO2 sensor: Optional
  • VOC sensor: Optional
  • PM2.5 sensor: Optional
Unit of measurement KOMFORT EC S5B 270-E S21
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 162
Unit current A 1.2
Maximum airflow m3/h 300
Sound pressure level LpA at 3 m dB(A) 34
Heat recovery efficiency, max % 94
Heat exchanger type - Counter flow
Heat exchanger material - Enthalpy
Weight kg 13.5
Extract filter - G4
Supply filter - G4 (option: F8)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 60
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Article - 8051210
Blauberg KOMFORT EC S5B 270-E S21 50 270 2016
Trademark Blauberg
Model KOMFORT EC S5B 270-E S21
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-77.8 A+ -40.2 A -16.1 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 80
Maximum flow rate (m3/h) 270
Electric power input (W) 153
Reference flow rate (m3/s) 0.053
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.316
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Declared typology RVU BVU
Sound power level (dB(A)) 50
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
749 212 167
The annual heating saved (AHS) (kWh/a) Cold Average Warm
8776 4486 2029
Datasheet
KOMFORT EC S5B 270 - data sheet
1.32 Mb
Datasheet
KOMFORT EC S5B 270-E S21 - energy label
96 Kb
Datasheet
KOMFORT EC S5B 270-E S21 - specification
76 Kb
Manual
KOMFORT EC S5(B) 270 - user's manual (B170-1EN-09)
2.46 Mb
Manual
S21 - user's manual (B55-8EN-05)
626 Kb
Manual
S14 - user's manual (B55-7EN-02)
1.31 Mb
Manual
Modbus table for connecting S21 automation to BMS - user's manual (B55-8-1EN-02)
141 Kb
Manual
S14 software "Zero Service Software"
18.32 Mb
BIM/CAD-models
KOMFORT EC S5B 270 - BIM model
668 Kb
Image
KOMFORT EC S5B 270-E S21 - image 1
348 Kb
ØD B H H1 L
125 590 852 893 316
Name Photo Description
Blauberg VKA 125 VKA 125 Air dampers for round ducts
Name Photo Description
Blauberg EVH 125-0.6-1 S21 V.2 EVH 125-0.6-1 S21 V.2 Electric duct preheater for heat exchanger freeze protection
Blauberg EVH 125-0.8-1 S21 V.2 EVH 125-0.8-1 S21 V.2 Electric duct preheater for heat exchanger freeze protection
Blauberg EVH 125-1.2-1 S21 V.2 EVH 125-1.2-1 S21 V.2 Electric duct preheater for heat exchanger freeze protection
Blauberg ENH 125-0.6-1 S21 V.2 ENH 125-0.6-1 S21 V.2 Duct heater for supply air reheating
Blauberg ENH 125-0.8-1 S21 V.2 ENH 125-0.8-1 S21 V.2 Duct heater for supply air reheating
Blauberg ENH 125-1.2-1 S21 V.2 ENH 125-1.2-1 S21 V.2 Duct heater for supply air reheating
Name Photo Description
Blauberg S25 S25 LCD control panel
Blauberg S22 S22 Control panels
Blauberg S22 Wi-Fi S22 Wi-Fi Control panels
Name Photo Description
Blauberg CD-1 CD-1 CO2 sensors
Blauberg CD-2 CD-2 CO2 sensors
Name Photo Description
Blauberg FS2 FS2 Humidity sensor
Other accessories
Name Photo Description
Blauberg FP 264x182x18 G4 FP 264x182x18 G4 G4 panel filter